Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Service Factor
1.15
Frame Material
Cast Iron
Voltage Rating
460
Hz
60 Hz
Frame Size
445T
Motor Application
Severe Duty
VoltCode
G
Full Load Pf
85
C Dimension
44.24 in
Phase
Three Phase
Full Load rpm
1785 rpm
Motor Shaft Length
8 1/2 in
Design
B
Mounting Style
F-1
Drive End Bearing
6319
Product Line
RG
Mult. Sym.
D3
Brake Feature
No
Full Load Efficiency
95.8 %
Full Load Amps
173
C Face Kit
18-1302
Washdown Duty
No
Motor Shaft Size
3 3/8 in
Epact Nominal Full Load Efficiency
95 %
Type
1888M
Enclosure
Totally Enclosed
Poles
4
Efficiency Group
Standard Efficient
Voltage
460
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Rotation
R
HP [Min]
150
Useable at 208V
No
Frame
445T
Open End Bearing
6314
RPM
1800 rpm
Mounting
Foot Mounted
Model
841 XL
RefPicture
CRUSH
Weight
1914.0 LB
EAN or UPC
781568196700
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back