Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Mounting Style
F-1
Mounting
Rigid Base
Useable at 208V
No
Frame Material
Cast Iron
Brake Feature
No
Rotation
R
Full Load Pf
92
C Face Kit
10-1305
Substitute Motor
M4108T-5
Full Load rpm
3520 rpm
Mult. Sym.
L1
Design
A
Service Factor
1.15
Motor Application
General Purpose
Poles
2
Phase
Three Phase
Hz
60 Hz
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Frame Size
Shaft Input, Not a C-Face
VoltCode
H
Washdown Duty
No
RPM
3600 rpm
Full Load Efficiency
93 %
Full Load Amps
26.2
Voltage
575
Motor Shaft Length
3 1/4 in
BALD Family Names
Premium Efficient, Nema Premium™
Voltage Rating
575
Enclosure
TEFC
Motor Shaft Size
1 5/8 in
C Dimension
26.39 in
Product Line
RG
Efficiency Group
Premium Efficient
Open End Bearing
6208
RefPicture
EMTECI
Frame
286TS
Drive End Bearing
6311
Type
0954M
Weight
418.0 LB
EAN or UPC
781568139127
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back