Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Full Load Efficiency
94.5 %
Brake Feature
No
Motor Application
Explosion Proof
Mounting Style
F-1
RPM
1800 rpm, 1500 rpm
VoltCode
U
Full Load rpm
1475 rpm, 1775 rpm
Useable at 208V
No
Phase
Three Phase
Voltage Rating
190, 460, 230, 380
Enclosure
XPFC
Mounting
Rigid Base
Frame Size
Shaft Input, Not a C-Face
Rotation
R
RefPicture
XPCI
Efficiency Group
Premium Efficient
Open End Bearing
6311
Service Factor
1
Frame
324T
Enclosure Designation
XPFC - Explosion Proof Fan Cooled
Hz
60 Hz, 50 Hz
Motor Shaft Size
2 1/8 in
Design
B
Washdown Duty
No
BALD Family Names
Premium Efficient, Explosion Proof
C Dimension
32.12 in
Product Line
RG
Voltage
190/380/230/460
Drive End Bearing
6312
Full Load Amps
46
Poles
4
Full Load Pf
86
Motor Shaft Length
5 1/4 in
Type
X1260M
Mult. Sym.
L1
Weight
834.0 LB
EAN or UPC
781568296011
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back