Full Load rpm
1770 rpm
Voltage Rating
460
RPM
1800 rpm
Frame
286T
Motor Shaft Size
1 7/8 in
Enclosure
Totally Enclosed
Efficiency Group
Standard Efficient
Poles
4
Mult. Sym.
L1
Mounting Style
F-1
Epact Nominal Full Load Efficiency
92.4 %
Model
XEX
Mounting
Foot Mounted
Brake Feature
No
Motor Application
Severe Duty
Motor Shaft Length
4 5/8 in
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
C Dimension
27.57 in
Full Load Pf
83
Full Load Efficiency
94.1 %
Frame Material
Cast Iron
Useable at 208V
No
Product Line
RG
Open End Bearing
6309
Full Load Amps
36
Rotation
R
VoltCode
G
Phase
Three Phase
Type
1060M
Voltage
460
C Face Kit
10-1305
Hz
60 Hz
Washdown Duty
No
Frame Size
286T
Design
B
Substitute Motor
CP4104T-4
RefPicture
ECP03
HP [Min]
30
Drive End Bearing
6311
Service Factor
1.15
Weight
470.0 LB
EAN or UPC
781568107447
NEMA Premium
My Applied Catalog