Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Type
1060M
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Useable at 208V
No
RPM
1800 rpm
Model
XEX
C Face Kit
10-1305
Frame Size
286T
Substitute Motor
CP4104T-4
Voltage Rating
460
Enclosure
Totally Enclosed
Motor Application
Severe Duty
Motor Shaft Length
4 5/8 in
Full Load Efficiency
94.1 %
C Dimension
27.57 in
Washdown Duty
No
Product Line
RG
Mult. Sym.
L1
Phase
Three Phase
Frame Material
Cast Iron
Hz
60 Hz
Mounting Style
F-1
HP [Min]
30
Service Factor
1.15
Efficiency Group
Standard Efficient
Mounting
Foot Mounted
Drive End Bearing
6311
Full Load Amps
36
Motor Shaft Size
1 7/8 in
RefPicture
ECP03
Rotation
R
Open End Bearing
6309
Design
B
Full Load Pf
83
Poles
4
Full Load rpm
1770 rpm
Frame
286T
VoltCode
G
Brake Feature
No
Voltage
460
Epact Nominal Full Load Efficiency
92.4 %
Weight
470.0 LB
EAN or UPC
781568107447
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back