Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Epact Nominal Full Load Efficiency
92.4 %
Voltage Rating
460
Mounting Style
F-1
Enclosure
Totally Enclosed
C Dimension
27.57 in
C Face Kit
10-1305
VoltCode
G
Rotation
R
Full Load Pf
83
Model
XEX
Mult. Sym.
L1
Type
1060M
RPM
1800 rpm
Open End Bearing
6309
Frame Material
Cast Iron
HP [Min]
30
Useable at 208V
No
Brake Feature
No
Phase
Three Phase
RefPicture
ECP03
Product Line
RG
Full Load Amps
36
Service Factor
1.15
Voltage
460
Drive End Bearing
6311
Substitute Motor
CP4104T-4
Hz
60 Hz
Full Load Efficiency
94.1 %
Frame
286T
Mounting
Foot Mounted
Motor Shaft Length
4 5/8 in
Design
B
Efficiency Group
Standard Efficient
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Full Load rpm
1770 rpm
Poles
4
Frame Size
286T
Washdown Duty
No
Motor Application
Severe Duty
Motor Shaft Size
1 7/8 in
Weight
470.0 LB
EAN or UPC
781568107447
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back