Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Mounting
Foot Mounted
Service Factor
1.15
C Face Kit
10-1305
Poles
4
Full Load Pf
83
Brake Feature
No
Product Line
RG
Frame Size
286T
Washdown Duty
No
Phase
Three Phase
Motor Shaft Length
4 5/8 in
Voltage
460
Substitute Motor
CP4104T-4
Mult. Sym.
L1
Useable at 208V
No
Model
XEX
VoltCode
G
Open End Bearing
6309
Hz
60 Hz
Design
B
Epact Nominal Full Load Efficiency
92.4 %
Full Load Amps
36
Drive End Bearing
6311
RefPicture
ECP03
Mounting Style
F-1
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Type
1060M
Full Load rpm
1770 rpm
Motor Application
Severe Duty
Full Load Efficiency
94.1 %
Rotation
R
Voltage Rating
460
Motor Shaft Size
1 7/8 in
Enclosure
Totally Enclosed
HP [Min]
30
RPM
1800 rpm
Efficiency Group
Standard Efficient
C Dimension
27.57 in
Frame Material
Cast Iron
Frame
286T
Weight
470.0 LB
EAN or UPC
781568107447
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back