Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
RefPicture
ECP03
Mounting Style
F-1
Service Factor
1.15
RPM
1800 rpm
Voltage Rating
460
Full Load Pf
83
Frame
286T
Motor Application
Severe Duty
HP [Min]
30
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Epact Nominal Full Load Efficiency
92.4 %
Design
B
Brake Feature
No
Mult. Sym.
L1
Full Load Efficiency
94.1 %
Useable at 208V
No
Washdown Duty
No
Rotation
R
Type
1060M
C Dimension
27.57 in
Drive End Bearing
6311
Phase
Three Phase
Mounting
Foot Mounted
Efficiency Group
Standard Efficient
Frame Material
Cast Iron
Motor Shaft Size
1 7/8 in
VoltCode
G
Model
XEX
Frame Size
286T
Hz
60 Hz
Full Load rpm
1770 rpm
C Face Kit
10-1305
Enclosure
Totally Enclosed
Substitute Motor
CP4104T-4
Voltage
460
Open End Bearing
6309
Poles
4
Product Line
RG
Motor Shaft Length
4 5/8 in
Full Load Amps
36
Weight
470.0 LB
EAN or UPC
781568107447
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back