Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Useable at 208V
No
Mult. Sym.
L1
HP [Min]
50
Product Line
RG
VoltCode
G
Hz
60 Hz
Voltage Rating
460
RefPicture
ECP03
Washdown Duty
No
Design
B
Motor Application
Severe Duty
Service Factor
1.15
RPM
1800 rpm
Model
XEX
Motor Shaft Length
5 1/4 in
Drive End Bearing
6312
Enclosure
Totally Enclosed
C Dimension
30 1/4 in
Frame
326T
Mounting Style
F-1
Epact Nominal Full Load Efficiency
93 %
Full Load Pf
87
Full Load rpm
1775 rpm
Full Load Amps
57
Open End Bearing
6311
Poles
4
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Frame Size
326T
C Face Kit
12-1105
Rotation
R
Frame Material
Cast Iron
Voltage
460
Phase
Three Phase
Type
1266M
Motor Shaft Size
2 1/8 in
Efficiency Group
Standard Efficient
Mounting
Foot Mounted
Brake Feature
No
Full Load Efficiency
94.5 %
Weight
643.0 LB
EAN or UPC
781568107553
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back