Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Rotation
R
Mounting Style
F-1
RefPicture
ECP03
C Dimension
30 1/4 in
Full Load Efficiency
94.5 %
Motor Shaft Size
2 1/8 in
Efficiency Group
Standard Efficient
Voltage
460
Mult. Sym.
L1
Useable at 208V
No
Full Load rpm
1775 rpm
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Hz
60 Hz
Poles
4
Drive End Bearing
6312
Frame
326T
Full Load Pf
87
Design
B
VoltCode
G
HP [Min]
50
Voltage Rating
460
Frame Material
Cast Iron
C Face Kit
12-1105
Model
XEX
Product Line
RG
Mounting
Foot Mounted
Motor Shaft Length
5 1/4 in
Motor Application
Severe Duty
Frame Size
326T
Type
1266M
Epact Nominal Full Load Efficiency
93 %
Brake Feature
No
Full Load Amps
57
Phase
Three Phase
Enclosure
Totally Enclosed
Open End Bearing
6311
Washdown Duty
No
Service Factor
1.15
RPM
1800 rpm
Weight
643.0 LB
EAN or UPC
781568107553
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back