Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
C Dimension
30 1/4 in
Hz
60 Hz
Model
XEX
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Rotation
R
RPM
1800 rpm
Design
B
HP [Min]
50
Mounting
Foot Mounted
Motor Shaft Length
5 1/4 in
Voltage
460
Type
1266M
Useable at 208V
No
RefPicture
ECP03
Motor Shaft Size
2 1/8 in
Washdown Duty
No
Epact Nominal Full Load Efficiency
93 %
Efficiency Group
Standard Efficient
Mult. Sym.
L1
Service Factor
1.15
Poles
4
Voltage Rating
460
Product Line
RG
Phase
Three Phase
Full Load Amps
57
Mounting Style
F-1
Full Load Pf
87
Frame
326T
Frame Material
Cast Iron
Frame Size
326T
Drive End Bearing
6312
Enclosure
Totally Enclosed
Motor Application
Severe Duty
VoltCode
G
Brake Feature
No
Full Load Efficiency
94.5 %
Open End Bearing
6311
C Face Kit
12-1105
Full Load rpm
1775 rpm
Weight
643.0 LB
EAN or UPC
781568107553
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back