Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Drive End Bearing
6309
Efficiency Group
Standard Efficient
Type
3956M
Voltage
230/460
Open End Bearing
6208
BALD Family Names
Premium Efficient, Nema Premium™
Voltage Rating
460, 230
Mounting Style
F-1
Motor Shaft Length
4 in
RefPicture
EMDP
Useable at 208V
Yes
Mult. Sym.
L1
Service Factor
1.15
Hz
60 Hz
Epact Nominal Full Load Efficiency
88.5 %
Motor Application
General Purpose
Design
B
Full Load rpm
1180 rpm
RPM
1200 rpm
Mounting
Rigid Base
Enclosure
OPSB
Full Load Efficiency
91.7 %
Product Line
RG
Poles
6
C Face Kit
39-1400
Rotation
R
VoltCode
E1
Full Load Pf
71
Substitute Motor
M2506T
Frame Size
Shaft Input, Not a C-Face
Washdown Duty
No
Frame Material
Steel
Frame
254T
Phase
Three Phase
C Dimension
21.69 in
Motor Shaft Size
1 5/8 in
Brake Feature
No
Enclosure Designation
OPSB - Open Slotted Band
Full Load Amps
10.7
Weight
239.0 LB
EAN or UPC
781568104712
NEMA Premium